Isolated Power Systems E900 Series

Wall mounted distribution board with integrated single phase isolation transformer, remote alarm indicator, test combination unit and optical on-line insulation fault location system for medical IT systems in accordance with IEC 60364-7-710, IEC 61557-8, IEC 61557-9 and DIN VDE 0100-710

 

 

  • A-Isometer® iso-MED427P with alarm indicator and test combination MK2430 and EDS151

  • A-Isometer® IR427 with alarm indicator and test combination MK7

Wall mounted distribution board with integrated single phase isolation transformer, remote alarm indicator, test combination unit and optical on-line insulation fault location system for medical IT systems in accordance with IEC 60364-7-710, IEC 61557-8,IEC 61557-9 and DIN VDE 0100-710

 

Distribution board features

·   Wall mounted front Perspex for front viewing

·   Insulation resistance, load current, temperature and PE connections monitoring

·   Main 2-pole circuit breakers

·   Sub-circuits with 2-pole circuit breakers

·   Power supply unit for alarm indicator and operator panels

·   Load current transformer

·   Terminals for incoming and outgoing cables

·   Fully factory wired and tested

·   Designed in accordance with the requirements of applicable standards

·   Exchange of information via bus technology


 

 

Product description

Isolated Power System E900 series is designed and manufactured to meet the latest requirements of supplying power to medical locations in accordance with IEC60364-7-710 .

A complete system with appropriate measuring current transformers, the E900 series is designed to provide the best solution for isolated power monitoring and supply.

Application

The IT system distribution board in the Isolated Power System E900 series supplies electrical power to group 2 medical locations in accordance with the IEC 60364-7-710 standards for circuits supplying to medical electrical equipment, systems intended for life support, surgical applications and other electrical equipment located in the “patients’ environment”.

In such locations, the use of the IT system with insulation monitoring and load current monitoring is mandatory. This applies to locations such as the anesthetic rooms, operating theatres, heart catheterization, intensive care units, angiographic examination rooms, premature baby rooms and etc.

 

 

 

 

Single-phase isolated transformer

 Bender Isolating transformers of the ES710 series for the power supply of single phase IT systems in accordance with IEC 60364-7- 710: 2002-11. A static screen is installed between the primary and secondary windings, which is connected to an isolated terminal. The mounting angles are isolated from the transformer core. Transformer is housed in a sheet steel enclosure.

Features:

The single-phase isolating transformers meet the requirements of the following standards: IEC 60364-7-710: 2002-11, DIN VDE 0100-710:2002-11, IEC 61558-1: 1997, DIN EN 61558-1 (VDE 0570-1): 1998, IEC 61558-2-15: 1999, DIN EN 61558-2-15 (VDE 0570-2-15): 2001

·   Rated power 3.15…10 kVA

·   Rated input voltage: AC 230V

·   Built-in temperature sensors

·   Low noise level < 35 dB (A)

·   High overload capability